2, 3, 3.5 and 4 core, armoured or unarmoured, 650/1100 V

XLPE Multicore Copper Power Cables

Multicore XLPE power cable with stranded compacted sector-shaped copper conductors, PVC inner sheath and galvanised steel armour where specified. The 3.5 core has a reduced neutral for balanced three phase distribution.

IS 7098 Part 1 650/1100 V AC / 1500 V DC to earth 2, 3, 3.5 and 4 core, 4 mm² to 400 mm²
  • XLPE insulation — 90 °C continuous, 250 °C short circuit
  • Galvanised steel flat strip or round wire armour to IS 3975
  • PVC Type ST2 inner and outer sheath, FRLS / FR / LSZH options
  • Sector shaped compacted conductors on larger sizes
  • Reduced neutral on the 3.5 core range
Construction IS 7098 Part 1
Conductor
Stranded compacted copper to IS 8130, class 1 or 2
Insulation
Cross-linked polyethylene (XLPE) to IS 7098-1
Inner sheath
Extruded PVC Type ST2 to IS 5831
Armour
Galvanised steel flat strip or round wire to IS 3975
Sheath
Extruded PVC Type ST2 / FRLS / FR / LSZH
Bending radius
12 × overall diameter, fixed installation

Schedules

Dimensions, weight and ratings

Dimensions in millimetres, weights in kg/km, currents in amperes. Tables scroll sideways on narrow screens.

Two core, unarmoured

17 rows
SizeClassInsulationSheathOverall dia.Weight (kg/km)
2 × 4Class 10.71.812.5165
2 × 6Class 10.71.813.5210
2 × 4Class 20.71.813175
2 × 6Class 20.71.814225
2 × 10Class 20.71.816300
2 × 16Class 20.71.814422
2 × 25Class 20.9217636
2 × 35Class 20.9219817
2 × 50Class 212211054
2 × 70Class 21.12231453
2 × 95Class 21.12.226.51966
2 × 120Class 21.22.228.52413
2 × 150Class 21.42.2322935
2 × 185Class 21.62.435.53676
2 × 240Class 21.72.639.54750
2 × 300Class 21.82.843.55918
2 × 400Class 223497495

Two core, flat strip armoured

11 rows
SizeInsulationArmourSheath (min.)Overall dia.Weight (kg/km)
2 × 250.94 × 0.81.418.5804
2 × 350.94 × 0.81.4201020
2 × 5014 × 0.81.422.51311
2 × 701.14 × 0.81.5625.51757
2 × 951.14 × 0.81.56282289
2 × 1201.24 × 0.81.5630.52755
2 × 1501.44 × 0.81.7231.83353
2 × 1851.64 × 0.81.72374094
2 × 2401.74 × 0.81.8838.75225
2 × 3001.84 × 0.82.0442.56412
2 × 40024 × 0.82.3648.28075

Two core, round wire armoured

17 rows
SizeClassInsulationArmourSheath (min.)Overall dia.Weight (kg/km)
2 × 4Class 10.71.41.2414408
2 × 4Class 20.71.41.2414.5427
2 × 6Class 10.71.41.2415484
2 × 6Class 20.71.41.2416522
2 × 10Class 20.71.41.2417.5665
2 × 16Class 20.71.41.417697
2 × 25Class 20.91.61.4201002
2 × 35Class 20.91.61.4221224
2 × 50Class 211.61.4241520
2 × 70Class 21.11.61.56272004
2 × 95Class 21.121.5630.52736
2 × 120Class 21.221.56333230
2 × 150Class 21.421.72363876
2 × 185Class 21.621.88404731
2 × 240Class 21.72.52.0442.46203
2 × 300Class 21.82.52.246.27514
2 × 400Class 222.52.3651.69262

Three core, unarmoured

17 rows
SizeClassInsulationSheathOverall dia.Weight (kg/km)
3 × 4Class 10.71.813210
3 × 4Class 20.71.813.5232
3 × 6Class 10.71.814280
3 × 6Class 20.71.815299
3 × 10Class 20.71.816.5415
3 × 16Class 20.71.816.2425
3 × 25Class 20.9219.5874
3 × 35Class 20.9221.51150
3 × 50Class 21224.51501
3 × 70Class 21.12.2282118
3 × 95Class 21.12.230.82821
3 × 120Class 21.22.233.83496
3 × 150Class 21.42.437.94322
3 × 185Class 21.62.6425377
3 × 240Class 21.72.846.96992
3 × 300Class 21.8351.58683
3 × 400Class 223.258.611029

Three core, flat strip armoured

12 rows
SizeInsulationArmourSheath (min.)Overall dia.Weight (kg/km)
3 × 160.74 × 0.81.2416.8772
3 × 250.94 × 0.81.420.11102
3 × 350.94 × 0.81.4221396
3 × 5014 × 0.81.424.81767
3 × 701.14 × 0.81.5628.52441
3 × 951.14 × 0.81.5631.33182
3 × 1201.24 × 0.81.5634.33895
3 × 1501.44 × 0.81.7238.34759
3 × 1851.64 × 0.81.8842.35852
3 × 2401.74 × 0.82.0447.37505
3 × 3001.84 × 0.82.251.89243
3 × 40024 × 0.82.5258.511704

Three core, round wire armoured

17 rows
SizeClassInsulationArmourSheath (min.)Overall dia.Weight (kg/km)
3 × 4Class 10.71.41.2415530
3 × 4Class 20.71.41.2416460
3 × 6Class 10.71.41.2416640
3 × 6Class 20.71.41.2417551
3 × 10Class 20.71.41.2419722
3 × 16Class 20.71.41.418.8921
3 × 25Class 20.91.61.421.71282
3 × 35Class 20.91.61.423.61596
3 × 50Class 211.61.5626.82042
3 × 70Class 21.11.61.5630.92888
3 × 95Class 21.121.5633.73686
3 × 120Class 21.221.72374455
3 × 150Class 21.421.8841.15396
3 × 185Class 21.622.04466868
3 × 240Class 21.72.52.250.98654
3 × 300Class 21.82.52.3655.510526
3 × 400Class 222.52.686413718

Three and a half core, unarmoured

11 rows
SizeInsulation (main/neutral)SheathOverall dia.Weight (kg/km)
3.5 × 250.9 / 0.7221.31035
3.5 × 350.9 / 0.7223.61311
3.5 × 501 / 0.9226.81748
3.5 × 701.1 / 0.92.2312460
3.5 × 951.1 / 12.234.33287
3.5 × 1201.2 / 1.12.237.64142
3.5 × 1501.4 / 1.12.442.34987
3.5 × 1851.6 / 1.12.646.86279
3.5 × 2401.7 / 1.22.852.48122
3.5 × 3001.8 / 1.435710079
3.5 × 4002 / 1.63.46512835

Three and a half core, flat strip armoured

11 rows
SizeInsulation (main/neutral)ArmourSheath (min.)Overall dia.Weight (kg/km)
3.5 × 250.9 / 0.74 × 0.81.421.91272
3.5 × 350.9 / 0.74 × 0.81.424.21586
3.5 × 501 / 0.94 × 0.81.427.42061
3.5 × 701.1 / 0.94 × 0.81.5631.52831
3.5 × 951.1 / 14 × 0.81.5634.83686
3.5 × 1201.2 / 1.14 × 0.81.7238.54617
3.5 × 1501.4 / 1.14 × 0.81.7242.75481
3.5 × 1851.6 / 1.14 × 0.81.8847.26830
3.5 × 2401.7 / 1.24 × 0.82.0452.78711
3.5 × 3001.8 / 1.44 × 0.82.257.910716
3.5 × 4002 / 1.64 × 0.82.5265.513556

Three and a half core, round wire armoured

11 rows
SizeInsulation (main/neutral)ArmourSheath (min.)Overall dia.Weight (kg/km)
3.5 × 250.9 / 0.71.61.423.61491
3.5 × 350.9 / 0.71.61.425.81824
3.5 × 501 / 0.91.61.56292337
3.5 × 701.1 / 0.921.5633.93296
3.5 × 951.1 / 121.5637.24237
3.5 × 1201.2 / 1.121.72415225
3.5 × 1501.4 / 1.121.88456194
3.5 × 1851.6 / 1.12.52.04507989
3.5 × 2401.7 / 1.22.52.25610003
3.5 × 3001.8 / 1.42.52.366112131
3.5 × 4002 / 1.63.152.687015817

Four core, unarmoured

16 rows
SizeClassInsulationSheathOverall dia.Weight (kg/km)
4 × 4Class 10.71.813.5260
4 × 6Class 10.71.814.7350
4 × 4Class 20.71.814.2280
4 × 6Class 20.71.815.5365
4 × 10Class 20.71.817.8510
4 × 16Class 20.71.817.5741
4 × 25Class 20.92211140
4 × 35Class 20.9223.51491
4 × 50Class 212261957
4 × 70Class 21.12.230.52774
4 × 95Class 21.12.233.53714
4 × 120Class 21.22.437.54645
4 × 150Class 21.42.6425719
4 × 185Class 21.62.846.57125
4 × 240Class 21.7352.59253
4 × 300Class 21.83.25811524

Four core, flat strip armoured

11 rows
SizeInsulationArmourSheath (min.)Overall dia.Weight (kg/km)
4 × 160.74 × 0.81.420969
4 × 250.94 × 0.81.4231406
4 × 350.94 × 0.81.4251786
4 × 5014 × 0.81.56282308
4 × 701.14 × 0.81.56323154
4 × 951.14 × 0.81.56354161
4 × 1201.24 × 0.81.72395101
4 × 1501.44 × 0.81.8843.56232
4 × 1851.64 × 0.82.04487676
4 × 2401.74 × 0.82.2549880
4 × 3001.84 × 0.82.3659.512198

Four core, round wire armoured

16 rows
SizeClassInsulationArmourSheath (min.)Overall dia.Weight (kg/km)
4 × 4Class 10.71.41.2415.3503
4 × 4Class 20.71.41.2416533
4 × 6Class 10.71.41.2416.5618
4 × 6Class 20.71.41.2417.3646
4 × 10Class 20.71.41.419.8870
4 × 16Class 20.71.61.4211159
4 × 25Class 20.91.61.4251615
4 × 35Class 20.91.61.426.52033
4 × 50Class 211.61.5629.52593
4 × 70Class 21.121.56343686
4 × 95Class 21.121.72384769
4 × 120Class 21.221.88425795
4 × 150Class 21.42.52.04477324
4 × 185Class 21.62.52.2528901
4 × 240Class 21.72.52.3657.511210
4 × 300Class 21.83.152.5264.514279

Current carrying capacity — 3, 3.5 and 4 core copper

15 rows
Size (mm²)Buried in groundIn ductsIn airMax. DC res. (Ω/km)
44538414.61
65647523.08
107462701.83
169579891.15
251221021190.727
351461221470.524
501731441790.387
702121772260.268
952542122790.193
1202872403200.153
1503212693650.124
1853623044220.0991
2404183525000.0754
3004693965740.0601
4005284476620.047

Air 40 °C, ground 30 °C, conductor 90 °C. To IS 3961 Part 6. Two core ratings run slightly higher — see the two core schedule or ask us.